Permit: T07CM00626

Parcel: 128100560

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM00626

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
10/31/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTE #2 AND COMPLY FROM 10/4/07 INSPECTION
AND NOTE 2 FROM 3/8/07 INSPECTION AND COMPLY
FAILURE TO COMPLY WITH NOTES ON INSPECTIONS FROM PAST WILL RESULT IN REINSPECTION FEES ON ALL PERMITS AT THIS SITE.
10/04/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE A MEANS TO CONTROL EXPANSION FOR TANK TYPE WATER HEATER
2. PROVIDE PROOF OF NEED FOR AIR ADMITTANCE VALVE AND INSTALL ON LONG RADIUS DRAINAGE FITTING IF REQUIRED OR REMOVE IF A VENT TIES INTO VENT SYSTEM.
03/08/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SHALL PROVIDE CLEANOUT FITTING ON EXISTING WYE BRANCH AT SINK AND PERM CAP CONTINUATION.
WATER HEATER TO BE ADDED TO PLAN AND VERIFIED FOR T&P TERMINATION. WATER SUPPLY TO BE MINIMUM 1/2" WITH SHUT OFF VALVE.