Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/23/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE ENERGY CONSERVATION CODE REQUIRES MIN. R5 DUCT INSULATION IN UNCONDITIONED SPACES. WHAT CODE IS YOUR ARCHITECT GETTING 4.2 INSULATION FROM? |
|
| 04/11/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE MIN. R5 DUCT LINER & FOIL WRAP ON ALL DUCT WORK INSIDE BLDG. 2. FOLD OVER ALL DOVE TAILS ON DRYER VENT START COLLAR 3. CHECKED CONDENSATE DRAIN. |