Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR TEMP C OF O 1. INSTALL SERVICE RECEPTACLE FOR ROOFTOP AC UNITS PER NEC 210.63 2. IDENTIFY GROUNDING CONDUCTOR AT ROOFTOP A/C UNIT #1 PER NEC 250.119 |
|
| 05/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RECALL WHEN METER INSTALLED & POWER IS ON TO SPACE 2. HAVE LADDER ON SITE |
|
| 05/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO POWER TURNED ON 2. HAVE LADDER ON SITE TO CHECK PREVIOUS ITEMS |