Permit: T07CM00621

Parcel: 13323190A


Addresses:

7812 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF
1. ISOLATE PRIMARY CONDUCTORS THROUGH AC UNIT
2. VERIFY IF 440.14 APPLIES
3. DO NOT PASS THROUGH DISCONNECT FOR SERVICE OUTLET

SPACE:
1. FINISH VDV CABELING
2. PLEASE VERIFY LISTING LABELING FOR EQUIPMENT
05/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CANNOT PASS 110V CORD THROUGH WALL -- 400.7 & 8
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS -- 314. 20
3. PANEL BOARD TO BE LABELED AS PER 404.8 -- NO ABBREVIATIONS.
4. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL
5. NO POWER AT THIS TIME
6. FINISH #1 (VDV CABELING) 5/10/07