Permit: T07CM00621

Parcel: 13323190A


Addresses:

7812 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/12/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/23/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/11/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
05/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
FINISH VDV CABELING

OK 2X4 LIGHTS
RECEIVED LETTER FOR CONDUIT
04/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS SUBJECT TO LETTER FROM ENGINEER
1. PLANS HAVE BOTH SPEC'S FOR CONDUIT SIZES
HAVE ENGINEER DETERMINE WHICH IS CORRECT.
04/03/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROPERLY THREAD 2 1/2" CONDUIT FITTING
2. PLANS CALL FOR 3/4" MIN. CONDUIT
3. WHERE ARE OUTLETS WEST WALL?
03/30/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
UNABLE TO LOCATE G.C PLEASE HAVE CONTACT NAME & NUMBER ON INSPECTION REQUEST FOR FUTURE INSPECTIONS.