Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/05/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES 1ST FLOOR |
|
| 06/29/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONDENSATE DRAINS DO NOT HAVE ADEQUATE SLOPE. FAN COILS SHOULD HAVE BEEN HUNG HIGHER TO PROVIDE SLOPE. PROVIDE MIN. 1/8" PER FT. SLOPE ID FAN COILS & DATA PLATES FINISH LOW VOLTAGE WIRING PROVIDE OVERFLOW SENSORS |
|
| 06/22/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) HARD LIDS 2ND FLOOR OK |
|
| 06/13/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND EXHAUST IN RESTROOMS OK TO SHEETROCK 2) SUSPENDED ROUGH DUCT OK TO PROCEED 3) CONDENSATE DRAINS NOT SLOPED CORRECTLY 4) PROVIDE MIN 1/8" PER FT SLOPE |
|
| 06/04/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |