Permit: T07CM00614

Parcel: 110035590

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/25/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/05/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES 1ST FLOOR
06/29/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CONDENSATE DRAINS DO NOT HAVE ADEQUATE SLOPE.
FAN COILS SHOULD HAVE BEEN HUNG HIGHER TO PROVIDE SLOPE. PROVIDE MIN. 1/8" PER FT. SLOPE
ID FAN COILS & DATA PLATES
FINISH LOW VOLTAGE WIRING
PROVIDE OVERFLOW SENSORS
06/22/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) HARD LIDS 2ND FLOOR OK
06/13/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPLY AND EXHAUST IN RESTROOMS OK TO SHEETROCK
2) SUSPENDED ROUGH DUCT OK TO PROCEED
3) CONDENSATE DRAINS NOT SLOPED CORRECTLY
4) PROVIDE MIN 1/8" PER FT SLOPE
06/04/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*