Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PER BUILDING OFFICIAL A PERMIT FOR OFFICE FURNITURE WILL BE NEEDED. INSPECTOR RESERVES RIGHT TO CHECK SITE FOR COMPLIANCE. OK FINAL. |
|
| 09/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) VDV CABELING LAYING ON LIGHT AND UNSUPPORTED 2) PROVIDE PERMIT FOR OFFICE FURNITURE TO RELEASE THIS SPACE FOR FINAL |
|
| 09/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH RECEPT COUNTER 2. USE APPROVED COVERS WITH FLOOR BOX 3. NEED TO SEE CONNECTIONS FOR OFFICE FURNITURE 4. PANEL SCHEDULES TO BE AS PER 408.4 - NO ABBREVIATIONS 5. SEAL FLOOR PENETRATIONS 6. FINISH VDV CABLING CONNECTIONS |