Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW AN ISOLATION GROUND AS WELL AS MECH GROUNDS, FURNITURE CONNECTIONS HAVE 2 GROUNDS ONE MECH ONE ISOLATION. NO ISOLATION GROUNDS PULLED. 2. J-BOXES UNDER FLOOR TO BE SECURED 3. MC CABLE TO BE SECURED WITHIN 12" OF J-BOXES 4. J-BOXES CONNECTED TO FURNITURE WHIPS TO BE SECURED & GROUNDED TO CONDUIT GROUND SYSTEM |