Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) SUBJECT TO DNR APPROVAL-OK PER RICHARD VIDAL |
|
| 03/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. A LISTED BRACE KIT REQUIRED FOR RISER 2. USE 1/4" BOLTS FOR RISER SUPPORT TO WALL 3. SUPPORT RECEPT. BOX UNDER PANEL 4. RISER CONDUCTORS TO BE FACTORY MARKED, SUNLIGHT RESISTANT, OTHER INFO PER NEC 5. INSTALL PERMANENT ADDRESS LABEL ON SERVICE 6. INSTALL GROUND RODS 2 AT 6' APART MIN. BOND WATER & GAS 7. HAVE COPY OF DNR REPORT ON SITE OR DNR TO CONTACT DAN SANTA CRUZ 909-5173 |