Permit: T07CM00567

Parcel: 120030120


Addresses:

1001 W LINCOLN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) SUBJECT TO DNR APPROVAL-OK PER RICHARD VIDAL
03/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. A LISTED BRACE KIT REQUIRED FOR RISER
2. USE 1/4" BOLTS FOR RISER SUPPORT TO WALL
3. SUPPORT RECEPT. BOX UNDER PANEL
4. RISER CONDUCTORS TO BE FACTORY MARKED, SUNLIGHT RESISTANT, OTHER INFO PER NEC
5. INSTALL PERMANENT ADDRESS LABEL ON SERVICE
6. INSTALL GROUND RODS 2 AT 6' APART MIN.
BOND WATER & GAS
7. HAVE COPY OF DNR REPORT ON SITE OR DNR TO CONTACT DAN SANTA CRUZ 909-5173