Permit: T07CM00566

Parcel: 140264510

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM00566

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/10/2007 FRAMING Approved IVRS - Inspection :*
04/09/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER SUPER
04/04/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DOCUMENTATION FOR CUT SLAB @ KITCHEN
2. PROVIDE MIN. 2" CLEARANCE BELOW WEEP SCREED @ FRONT PORCH
3. REPAIR OVERNOTCHED TOP PLATE IN GARAGE & OVERNOTCHED STUDS IN M. BATH
4. SECURE BOOT FOR R.A.G IN HALLWAY
5. SEAL VAPOR BARRIER IN FRONT BEDROOM & THROUGHOUT
6. PROVIDE MIN. 10' CLEARANCE FROM PLUMBING VENT TO FRESH AIR INTAKE
7. PLAN INCOMPLETE -- STOPPED INSPECTION.