Permit: T07CM00562

Parcel: 140553900

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
05/09/2007 SHEET ROCK NAILING Approved IVRS - Inspection :*
05/08/2007 SHEET ROCK NAILING Denied IVRS - Inspection :
The drywall is not nailed per code.| 175*
1) GARAGE LIDE UNDER OCCUPIED SPACE MUST HAVE 1 7/8" NAILS OR SCREWS AT 6" ON CENTER
2) GARAGE SHEARWALL 3 MUST BE NAILED AT 4" ON CENTER
3) KITCHEN SHEARWALL 1 MISSING TWO STUDS NAILED
4) MBR SHEARWALL 1 NOT NAILED AT 7" ON CENTER TOP PLATE
5) M. CLOSET #1 SHEAR NOT NAILED
6) BEDROOMS 2 & 3 #1 SHEARWALLS NOT NAILED