Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/02/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/26/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM 3 OF 4/27/07 NOT DONE 2) ITEM 1 OF 4/24/07 POST TO SHORT-NOT CARRYING LOAD 3) HANGERS NOT CARRYING LOAD |
|
| 04/24/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL 2 X 4 POST REQUIRED UNDER EXTENDED STAIR ? 2) NAIL SHEARWALLS PLATES AT 4" ON CENTER 3) FIRST FLOOR SHEARWALLS REQUIRE EPOXY SET BOLTS-NOT WEDGE ANCHORS 4) STAPLE IN PEX NORTH WALL |
|
| 04/20/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BANG PLATE ROMEX GARAGE TOP PLATE AT H20 HTR 2) STAPLE IN PEX NORTH WALL DINING ROOM 3) WEST WALL 1ST FLOOR SUPPORT PT LOAD GIRDER FROM ABOVE 4) 2ND FLOOR SHEARWALLS NAIL PLATES PER PLAN, #9=4" ON CENTER 16D'S 5) BLOCKS FOR SHEETROCK AT TUB SIDES 6) ATTIC, DUCTS MISSING FROM UNIT, CONDENSATE LINE NOT COMPLETE 7) NOTE II SHEAR SCHEDULE DON'T WEDGE ANCHORS AT EXT. WALLS 8) NO DETAIL ON PLAN, 2ND FLOOR FRONT POP OUT BEARING BETWEEN TRUSSES ADD BLKS FOR SUPPORT |