Permit: T07CM00562

Parcel: 140553900

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/11/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/09/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL PERIMETER OF SOUTHWEST SHEARWALL
2) RSP4'S NEEDED SOUTHWEST MAIN FLOOR CORNER
3) MINIMUM 2 ANCHOR BOLTS ON BOTTOM PLATES OF FRONT COLUMNS
4) RSP4 NEEDED FRONT ENTRANCE GARAGE WALL
5) HTT16 NEEDED ON HOUSE/GARAGE SHEARWALL NEXT TO GARAGE SERVICE DOOR
6) COIL STRAP BEAM TO FRONT COLUMNS
7) KING STUD MISSING NORTH SIDE FRONT ENTRANCE
8) CARRY BEARING TO FOUNDATION UNDER A13G GIRDER
03/22/2007 EXT METAL CLIPS/EXT SHEATHING Cancelled IVRS - RI canceled