Permit: T07CM00558

Parcel: 141015280

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM00558

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/23/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MISSING COVER ON CONDULETS ON ROOF
2. LOOSE COMPRESSION FITTINGS ON EMT
3. ON SET OF PV MODULES IS LOOSE ON STAND
4. NEED TO GROUND EACH PV MODULE AT GROUND POINTS PER MANUFACTURE.
5. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUNDS
6. GROUNDS TO BE TWISTED TOGETHER BEFORE INSTALLING BARREL CRIMP
7. PROVIDE LISTING OF BARREL CRIMP THAT IT CAN BE USED OUTDOORS
8. STRAP EMT WITHIN 3' OF CONDULETS (LB'S)
9. CHECK WIRE FILL ON BELL BOXES. APPEARS TO BE TOO MANY WIRES IN SOME BOXES.
10. RECALL WHEN READY
11. PROVIDE LISTING OF GROUNDING CLIPS. WILL NOT ACCEPT IF NOT LISTED.