Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00549
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1. OPEN TILES IN ROOMS TO FINISH INSPECTING VDV CABLING 2. FINISH VDV CABLING |
|
03/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11 2. PLEASE VERIFY IF FLEX CONNECTOR IS FOR OVER 250V USAGE 3. BONDING AT CONCENTRIC PER 250.97 4. NOTE: CEILING IS A PLENUM |
|
03/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROTECT TOP PLATES FOR VDV CABLING OK WALLS EXCEPT AS NOTED |
|
03/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT M/C CABLE & FLEX AT SHALLOW STUDS |