Permit: T07CM00549

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM00549

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1. OPEN TILES IN ROOMS TO FINISH INSPECTING VDV CABLING
2. FINISH VDV CABLING
03/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. VDV CABLING TO BE AS PER 725.3 & 6, 800.3 & 6, 300.11
2. PLEASE VERIFY IF FLEX CONNECTOR IS FOR OVER 250V USAGE
3. BONDING AT CONCENTRIC PER 250.97
4. NOTE: CEILING IS A PLENUM
03/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROTECT TOP PLATES FOR VDV CABLING
OK WALLS EXCEPT AS NOTED
03/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT M/C CABLE & FLEX AT SHALLOW STUDS