Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/09/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 4" SEWER REQUIRES 4" CLEANOUT CAP NOT 3" 2) OUTSIDE HOSE BIBS REQUIRE NON REMOVABLE ANTI-SIPHON ON VALVE 3) REAR PORCH GAS LINE REQUIRES A SHUT OFF VALVE WITH CAP 4) NO FURNACE INSTALLATION MANUAL ON SITE PAGE 10 OF LAST GOODMAN MANUAL-I SAW REQUIRES DBL WALL VENT TO BE CONNECTED 1/2" OUTSIDE OF CABINET. PROVIDE INSTALLATION MANUAL AND COMPLY 5) STOPPED INSPECTION |