Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00531

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL EXTENSIONS ON BOXES MORE THAN 1/4" BACK
2. RECEPTACLES TO EXTEND PAST METAL PLATES
3. INSTALL PROTECTIVE BUSHINGS ON WIRES LARGER
THAN #4
4. INSTALL DISCONNECTS ON FAN COIL UNITS IN WALK INS
5. INSTALL DISCONNECTS ON HOT WATER DISPENSING UNITS
6. ALL 15 & 20 AMP RECEPTACLES (120V) IN KITCHEN TO BE GFI PROTECTED SEE NOTE K ON SHEET E3.0
7. MARK BREAKERS AT SES
8. NEED SERVICE RECEPT ON ROOF FOR A/C & ROOFING EQUIPMENT
9. CANNOT USE MACHINE SCREW FOR GROUNDING CONNECTION
10. SOME OUTSIDE & POLE LIGHTS NOT WORKING
11. EM LIGHTING NOT OPERATING/NOT PER PLAN
12. PROVIDE DISCONNECT FOR MENU BOARD SIGN
13. CONNECT GROUNDS TO POLE LIGHTS
14. SEAL ALL RACEWAYS INTO COOLERS
15. SECURE RACEWAYS INTO COOLERS