Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00531
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL EXTENSIONS ON BOXES MORE THAN 1/4" BACK 2. RECEPTACLES TO EXTEND PAST METAL PLATES 3. INSTALL PROTECTIVE BUSHINGS ON WIRES LARGER THAN #4 4. INSTALL DISCONNECTS ON FAN COIL UNITS IN WALK INS 5. INSTALL DISCONNECTS ON HOT WATER DISPENSING UNITS 6. ALL 15 & 20 AMP RECEPTACLES (120V) IN KITCHEN TO BE GFI PROTECTED SEE NOTE K ON SHEET E3.0 7. MARK BREAKERS AT SES 8. NEED SERVICE RECEPT ON ROOF FOR A/C & ROOFING EQUIPMENT 9. CANNOT USE MACHINE SCREW FOR GROUNDING CONNECTION 10. SOME OUTSIDE & POLE LIGHTS NOT WORKING 11. EM LIGHTING NOT OPERATING/NOT PER PLAN 12. PROVIDE DISCONNECT FOR MENU BOARD SIGN 13. CONNECT GROUNDS TO POLE LIGHTS 14. SEAL ALL RACEWAYS INTO COOLERS 15. SECURE RACEWAYS INTO COOLERS |