Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T07CM00531
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2007 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
10/23/2007 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE FROM CONTRACTOR |
|
10/22/2007 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LETTER OF TORQUE FOR SWITCH GEAR 2. INSTALL PROTECTIVE BUSHING ON ENDS OF PVC NEC 352.46 3. PLAN DOES NOT SHOW CONDUCTOR SIZE FROM XFMR TO SES 4. REMOVE EQUIPMENT GROUNDING CONDUCTORS FROM SES TO TEP XFMR -- NEC 250.6 5. BOLT DOWN FRONT SECTION OF SES 6. CHECK CONDUCTORS TO PANELS/EQUIPMENT NOT SIZED PER PLAN |