Permit: T07CM00522

Parcel: 141353300


Addresses:

6010 S JAKEMP TR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM00522

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2007 FRAMING Approved IVRS - Inspection :*
06/08/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLOOR ALL WET FROM DWV TEST
2) USE CORRECT FHA STRAP OVER HOODE VENT (16 GUAGE) IN KITCHEN
06/07/2007 FRAMING Denied 1) FILL ALL HOLES IN FHA PLATES WITH 16D NAILS
2) SEAL AROUND PENETRATIONS IN FLOOR TRUSS ? STOP
3) OVERNOTCHED 2 X 4 BEARING WALL MAIN FLOOR INTERIOR AND EXTERIOR MASTER BEDROOM
4) PROPER FHA STRAPS FOR BEARING INTERIOR WALL IN KITCHEN
05/22/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OVER NOTCHED STUD SOUTH WALL IN GARAGE
2) PROPER NAILS AND SIZE IN FHA STRAPS
3) BLOCK REGISTER MASTER TOILET ROOM AND UPSTAIRS
4) DRAFT STOP FLOOR TRUSSES MAXIMUM 1000 SQ FT
5) FIX WIRES AT KITCHEN HALL INTO WALL
6) SUPPORT DRAIN LINE ABOVE UTILITY ROOM
7) BOND GAS LINE