Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM00485
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* ON FINAL I.D FAN COILS & CONDENSORS RELOCATE DISCONNECT NORTH AIR HANDLER PROVIDE AN AIR BALANCE REPORT |
|
03/13/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED |