Permit: T07CM00477

Parcel: 133351610


Addresses:

702 N BEDFORD DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAINTAIN WORKING CLEARANCES 110.26
2. USE FITTING FOR WET LOCATION
3. SUPPORT CONDUIT AS PER CODE -- WALLS & ROOF
4. TIGHTEN LOOSE FITTINGS - CONDUIT & CORDS
5. BREAKER TO BE LISTED FOR USE BY MANUFACTURE OF PANEL
6. SPLICES TO BE SIZED PER LISTING
7. UNCOVER FITTINGS AT ROOF TRANSITIONS TO INSPECT
8. LABEL BREAKER
9. GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED
PER 250.122 TO TERMINATION.
10. USE APPROVED SPLICE METHODS FOR T-STAT WIRING
11. WHERE DOES PUMP PLUG INTO?
12. MISSING JUNCTION BOX COVER
13. PLEASE VERIFY SERVICE LOAD