Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAINTAIN WORKING CLEARANCES 110.26 2. USE FITTING FOR WET LOCATION 3. SUPPORT CONDUIT AS PER CODE -- WALLS & ROOF 4. TIGHTEN LOOSE FITTINGS - CONDUIT & CORDS 5. BREAKER TO BE LISTED FOR USE BY MANUFACTURE OF PANEL 6. SPLICES TO BE SIZED PER LISTING 7. UNCOVER FITTINGS AT ROOF TRANSITIONS TO INSPECT 8. LABEL BREAKER 9. GROUNDING EQUIPMENT CONDUCTOR TO BE SIZED PER 250.122 TO TERMINATION. 10. USE APPROVED SPLICE METHODS FOR T-STAT WIRING 11. WHERE DOES PUMP PLUG INTO? 12. MISSING JUNCTION BOX COVER 13. PLEASE VERIFY SERVICE LOAD |