Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 03/14/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO UFER 2) WRONG PLAN MUST HAVE T04-M-0172 NOT T05-M-0108 |
|
| 03/13/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1) INCORRECT PLAN-NEED CITY OF TUCSON PLAN TD #16-09-30 OR T04-M0172 NOT T05-M0108 |
|
| 03/09/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHIM HEADERS 2. DOUBLE 2X POST REQUIRED ENTRY STAIR HEADER 3. DOUBLE RINGS REQUIRE ENTRY 4. RIBBON ABOVE WEST SIDE SHEAR 5. FIRST TO SECOND FLOOR CONNECTION REQUIRES CS2D STRAPS AT 32" O.C PER SN1 6. STRAP TOP PLATE TO BEAM PER (9/SD2) 7. POST GIRDER TO SLAB AT STAIR 8. HEADERS REQUIRE 2-2X 9. NAIL SHEAR WALL PLATE 2ND FLOOR 3" O.C 10. SHEAR WALL 10 REQUIRES ANCHOR BOLTS AT 24" O.C UNDER STAIR. |