Permit: T07CM00472

Parcel: 12913208B


Addresses:

1215 E 33RD ST #02

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/21/2007 FRAMING Approved IVRS - Inspection :*
05/20/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) C.P. BEAM SIZE NOT AS PER PLAN
2) BEAM SHALL NOT BEAR OVER WINDOW, ENGINEERING REQUIRED TO JUSTIFY IMPOSED LOAD ON ? LINTELS
3) TERMINATE DRYER VENT AT T-TOP AND PROTECT WITH BANG PLATE
4) BLOCK 3 SIDES AIR GRILLS
5) REMOVE AND REPAIR BROKEN CMU AT C.P. COL.
6) SEAL GAP AT TOP PLATE AT FURR OUT
7) PROVIDE APPROVED TRUSS SPECS
8) BOLTS MISSING AT TOP PLATE TO CMU 12" MAX FROM EDGE
9) 3 NAILS REQUIRED TOP CORD CRIPPLE JACKS