Permit: T07CM00453

Parcel: 141096780

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM00453

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/06/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/04/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER HEATER VENT MUST EXTEND A MINIMUM OF 12" ABOVE ROOF ON SHORT SIDE TO BOTTOM OF WEATHERCAP
2. NO GAS PRESSURE TEST
3. MISSING CLEANOUT HALL TUB