Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* LOCKED NO ACCESS LEFT MESSAGE ON PHONE # |
|
| 04/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) VERIFY ROMEX IN CONDUIT FOR DAMAGE 2) IDENTIFY CONDUCTORS FOR 200.7 3) JUNCTION BOX TO BE ACCESSIBLE 4) USE APPROVED TERMINATIONS FOR GROUND EQUIPMENT CONDUCTOR 5) BOXES MORE THAN 1/4" FROM BOX TO SURFACE. NEED APPROVED EXTENDER RINGS 314.20 6) LABEL SERVICE DISCONNECT 7) FUSES TO BE SERVICE RATED AND INSTALL REJECTION PINS 8) REPLACE MISSING GROUNDING ELECTRODE CONDUCTOR |