Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM00420

Parcel: 11015123C


Addresses:

5541 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00420

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
LOCKED NO ACCESS
LEFT MESSAGE ON PHONE #
04/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) VERIFY ROMEX IN CONDUIT FOR DAMAGE
2) IDENTIFY CONDUCTORS FOR 200.7
3) JUNCTION BOX TO BE ACCESSIBLE
4) USE APPROVED TERMINATIONS FOR GROUND EQUIPMENT CONDUCTOR
5) BOXES MORE THAN 1/4" FROM BOX TO SURFACE. NEED APPROVED EXTENDER RINGS 314.20
6) LABEL SERVICE DISCONNECT
7) FUSES TO BE SERVICE RATED AND INSTALL REJECTION PINS
8) REPLACE MISSING GROUNDING ELECTRODE CONDUCTOR