Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00417
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/26/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/09/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE EX. FAN TO GRID 2. PLANS SHOW 2 FIXTURES IN THE CEILING 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND SUPPORTED OFF GRID 4. NEED SUPPORT WIRES FOR LIGHT FIXTURES, FIXTURE HAS OPEN WIRING AT END 5. TAKE A LOOK AT WIRING FOR RECEPTION AREA TRACK LIGHTING. SOMEONE HAS WIRED THEM WITH AN EXTENSION CORD AND OPEN SPLICES IN CEILING. |