Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00411
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/09/2007 | ELECTRIC - FINAL | Denied | AC #13 1. INSTALL PROPER SIZE FUSES - NEC 240, 310 2. 2 CONDUCTORS NOT ALLOWED UNDER GROUND LUG NEC 110.3 B 3. PROPERLY IDENTIFY EQUIPMENT GROUNDS - NEC 250.119 4. NEED BONDING BUSHINGS ON RACEWAYS OVER 250V WITH CONCENTRICS - NEC 250.97 5. STRAP FLEX GOING INTO UNIT - NEC 350.30 AC #14 1. PROVIDE SERVICE RECEPTACLE - NEC 210.63 2. STRAP FLEX - NEC 350.30 3. 2 CONDUCTORS UNDERGROUND LUG NOT ALLOWED NEC 110.3 B 4. NEED BOND BUSHING -- NEC 250.97 INSIDE 1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN 2. CORRECTLY IDENTIFY ALL PANEL DIRECTORYS AND MAKE MORE PERMANENT - NEC 408.4 3. BREAKERS TO BE 6'7" MAX ABOVE FLOOR (PANEL UPB) NEC 404.8 4. HAVE SEVERAL LOOSE RECEPTACLES, ALSO, INSTALL ALL COVERS AND INSTALL ARC SHIELDS AS NEEDED 5. CKT'S FOR FRONT ENTRY RECEPTACLES DEAD DO NOT CALL BEFORE ALL COMPLETE THIS SPACE IS NOT TO BE OCCUPIED BEFORE APPROVAL. |