Permit: T07CM00411

Parcel: 10408078C


Addresses:

660 W AUTO MALL DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00411

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/09/2007 ELECTRIC - FINAL Denied AC #13
1. INSTALL PROPER SIZE FUSES - NEC 240, 310
2. 2 CONDUCTORS NOT ALLOWED UNDER GROUND LUG
NEC 110.3 B
3. PROPERLY IDENTIFY EQUIPMENT GROUNDS - NEC 250.119
4. NEED BONDING BUSHINGS ON RACEWAYS OVER 250V WITH CONCENTRICS - NEC 250.97
5. STRAP FLEX GOING INTO UNIT - NEC 350.30

AC #14
1. PROVIDE SERVICE RECEPTACLE - NEC 210.63
2. STRAP FLEX - NEC 350.30
3. 2 CONDUCTORS UNDERGROUND LUG NOT ALLOWED
NEC 110.3 B
4. NEED BOND BUSHING -- NEC 250.97

INSIDE
1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN
2. CORRECTLY IDENTIFY ALL PANEL DIRECTORYS AND MAKE MORE PERMANENT - NEC 408.4
3. BREAKERS TO BE 6'7" MAX ABOVE FLOOR (PANEL UPB)
NEC 404.8
4. HAVE SEVERAL LOOSE RECEPTACLES, ALSO, INSTALL ALL COVERS AND INSTALL ARC SHIELDS AS NEEDED
5. CKT'S FOR FRONT ENTRY RECEPTACLES DEAD

DO NOT CALL BEFORE ALL COMPLETE
THIS SPACE IS NOT TO BE OCCUPIED BEFORE APPROVAL.