Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00411
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL USED CAR NEW CONSTRUCTION AREA |
|
04/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES NOT PROPERLY MOUNTED -- NEC 314.23 A1 2. FINISH DEMO AND WIRING 3. UNDERGROUND COVERED BEFORE INSPECTION 4. WALL COVERED BEFORE INSPECTION 5. STRAP MC WITHIN 12" OF TERMINATIONS - NEC 330.30 6. STRAP EMT WITHIN 3' OF BOXES - ENC 358.30 7. INSTALL NAIL PLATES - NEC 330.17 8. CHECK BOX FILL -- NEC 314.16 |