Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 01/18/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HI-BAY LIGHTING NOT AS PER PLAN - TYPE & BATT BACK UP 2. CONDUCTORS TO BE COLOR CODED PER CITY AMENDMENT 210.5 3. WHERE IS DETAIL FOR OTHER CONTACTORS AND CONTROLS? 4. CONTACTORS ARE RECOGNIZED COMPONENT MARKINGS. WHAT LISTED ASSEMBLY ARE THEY BEING USED IN? 5. PANEL SCHEDULE & LIGHTING CIRCUITS NOT AS PER PLAN WHAT ARE LOADS AND CIRCUITING 6. OUTSIDE EM LIGHTS TO BE AS PER 700.12 7. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 8. CLEAN EXCESS PAINT FROM DEVICE TERMINAL SCREWS 110.12 9. PLANS CALL FOR STAINLESS PLATES |
|
| 01/08/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |