Permit: T07CM00407

Parcel: 12213011A


Addresses:

1124 N BRYANT AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T07CM00407

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/18/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. HI-BAY LIGHTING NOT AS PER PLAN - TYPE & BATT BACK UP
2. CONDUCTORS TO BE COLOR CODED PER
CITY AMENDMENT 210.5
3. WHERE IS DETAIL FOR OTHER CONTACTORS AND CONTROLS?
4. CONTACTORS ARE RECOGNIZED COMPONENT MARKINGS. WHAT LISTED ASSEMBLY ARE THEY BEING USED IN?
5. PANEL SCHEDULE & LIGHTING CIRCUITS NOT AS PER PLAN WHAT ARE LOADS AND CIRCUITING
6. OUTSIDE EM LIGHTS TO BE AS PER 700.12
7. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
8. CLEAN EXCESS PAINT FROM DEVICE TERMINAL
SCREWS 110.12
9. PLANS CALL FOR STAINLESS PLATES
01/08/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*