Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 03/27/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PANEL SCHEDULE AND WIRING PER PLANS DO NOT MATCH IF CIRCUITS NOT RUN AS PER PLANS PLEASE REVISE PLANS. |
|
| 03/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FINISH VDV CABELING 300.11 2) INSTALL ALL DEVICES 3) CONDUCTORS TO BE IDENTIFIED PER 200.7 AND FOR 277V 310.5 (C) 4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 5) FINISH INSTALLING HALL LIGHTS 6) REVISE PANEL SCHEDULES-NO ABREVATIONS 408.4 7) FILL UNUSED OPENINGS IN PANEL COVERS |