Permit: T07CM00387

Parcel: 141353470


Addresses:

6011 S JAKEMP TR


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T07CM00387

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2007 BUILDING - FINAL Approved IVRS - Inspection :*
06/27/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL POST TENSION AT SPIGOT
2) ONLY 1-#4 COPPER AT PANEL, MISSING UFER OR BOND
3) SHOW CONNECTIONS
4) MAX 25 AMP BREAKER FOR WATER HEATER
5) ANTI-TIP ON STOVE