Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T07CM00386
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2007 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 09/07/2007 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | ||
| 09/06/2007 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FOOTING TO BE 12" INTO NATURAL GRADE AND ALL THE WAY TO THE FORMS 2) #4 REBAR REQUIRES MINIMUM 20" OVERLAP 3) NEED 3" CLEAR REBAR TO DIRT 4) INSTALL DOWELS PER PLAN NORTH SIDE ADDITION |