Permit: T07CM00384

Parcel: 13336014G


Addresses:

9725 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM00384

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/14/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RWL STILL HAS BACKPITCH. CORRECT PRIOR TO NEXT INSPECTION. FAILURE TO COMPLY WILL RESULT IN REINSPECTION FEES. WALLS OK TO COVER.
12/07/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 12/5/07
12/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
TEST ON RWLS OK
CORRECT SLOPE ON RWLS SUPPORT PIPING ON EAST SIDE
CLAMP OVERHEAD WATER PIPING. SUPPORT AT 6' MAX
TEST ON COPPER AND DWV OK
INSULATE COPPER PER SPEC 15220 AND 15025
GAS PIPING W/TEST INSIDE BUILDING OK
12/04/2007 PLUMBING - INTERMEDIATE Denied - RWL HAS LEAK
- SUPPORTS REQUIRE CLAMPS
- MIDSTORY SUPPORTS REQUIRED
- SECURE PIPING AT OUTLETS
- BACKING FOR MS BRACKET
- ISOLATE CU FROM ALL METALS
- REMOVE FLUX RESIDUE
- NH COUPLINGS NOT APPROVED FOR PVC
- HAMMER ARRESTORS PER PLAN
- TEST THRU LOG LIGHTER VALVE
11/29/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ABV CEILING RMS 128 & 129 OK
11/26/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/13/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ALL WORK BEFORE CALLING FOR INSPECTION