Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00384
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK OUTSIDE CANS DRIVE THRU OK CANS SOFFITS TELLERS, WAITING LOBBY |
|
11/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS FINISH INSTALLING FAR SIDE SUPPORT |
|
11/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE FOUR SIDE BOX SUPPORT 2) SECURE MC CABLE WITHIN 12" OF BOXES 3) CHECK MC CONNECTORS TIGHT AROUND CABLES 4) GROUND ALL METAL BOXES 5) DO NOT RUN MC CABLE INSIDE CHANNEL-NEED 1 1/4" CLEARANCE TO CABLES 6) NEED 1 1/4" CLEARANCE TO CABLES RUNNING PARALLEL WITH METAL STUDS 7) CHECK FOR DEPTH OF BOXES ON CEMENT/BLOCK WALLS ? 2" OF FOAM AND 5/8" ROCK BEING INSTALLED |
|
08/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 6 FLOOR BOXES AND ASSOCIATED 3/4" AND 1" PVC IN BLDG SLAB |
|
08/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PVC RACEWAYS IN BUILDING SLAB 2. OK 1 - 4" PVC FROM TEP X-FMR TO BUILDING SES 3. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTORS PER NEC 300.5 |