Permit: T07CM00384

Parcel: 13336014G


Addresses:

9725 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM00384

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OUTSIDE CANS DRIVE THRU
OK CANS SOFFITS TELLERS, WAITING LOBBY
11/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS FINISH INSTALLING FAR SIDE SUPPORT
11/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE FOUR SIDE BOX SUPPORT
2) SECURE MC CABLE WITHIN 12" OF BOXES
3) CHECK MC CONNECTORS TIGHT AROUND CABLES
4) GROUND ALL METAL BOXES
5) DO NOT RUN MC CABLE INSIDE CHANNEL-NEED 1 1/4" CLEARANCE TO CABLES
6) NEED 1 1/4" CLEARANCE TO CABLES RUNNING PARALLEL WITH METAL STUDS
7) CHECK FOR DEPTH OF BOXES ON CEMENT/BLOCK WALLS ? 2" OF FOAM AND 5/8" ROCK BEING INSTALLED
08/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 6 FLOOR BOXES AND ASSOCIATED 3/4" AND 1" PVC IN BLDG SLAB
08/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PVC RACEWAYS IN BUILDING SLAB
2. OK 1 - 4" PVC FROM TEP X-FMR TO BUILDING SES
3. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTORS PER NEC 300.5