Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00364
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CHECK EMERGENCY LIGHTING - MAKE SURE IT IS WORKING, PER PLAN AND ENERGIZED BY LIGHTING CKT FEEDING THAT AREA -- NEC 700.12 2. PROVIDE DISCONNECTING MEANS FOR INSTA-HOT NEC 422.31B 3. OVER-CURRENT PROTECTIVE DEVICE FOR INSTA-HOT TO HIGH -- NEC 422.11E |
|
04/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |