Permit: T07CM00364

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00364

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/25/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CHECK EMERGENCY LIGHTING - MAKE SURE IT IS WORKING, PER PLAN AND ENERGIZED BY LIGHTING CKT FEEDING THAT AREA -- NEC 700.12
2. PROVIDE DISCONNECTING MEANS FOR INSTA-HOT
NEC 422.31B
3. OVER-CURRENT PROTECTIVE DEVICE FOR INSTA-HOT TO HIGH -- NEC 422.11E
04/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*