Permit: T07CM00363

Parcel: 13204271A


Addresses:

3285 E 44TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
06/21/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1. STRAP ALL FLEX UP OFF OF GRID & LIGHTS. BE SURE ALL STRAPS ARE MIN. 1 1/2" WIDE
2. DUCT CONNECTIONS NOT PER PLAN. BE SURE ALL DUCT TAPE IS UL181 A OR B LISTED.
3. PROVIDE SECONDARY DRAINS OR OVERFLOW SENSORS ON ALL FAN COILS. OK PARTIAL CEILING TILES.

PERMANENTLY I.D FAN COILS & CONDENSORS