Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND BUSHINGS NEEDED AT CONCENTRICS 250.97 2. MAINTAIN SPACE ABOVE DISCONNECT 110.26 3. DISCONNECT TO BE WITHIN SIGHT FROM METER 430.102(B) 4. EQUIPMENT LOCATIONS NOT AS PER PLANS PLEASE LOCATE AS INSTALLED LOCATIONS, PANELS, PUMPS, RECEPTACLES AND JUNCTION BOXES. |