Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00326
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE 1. WAITING ON PAPERWORK FOR TRANSFORMERS |
|
| 03/23/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 03/22/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6, 760.3 & 6 2. WE HAVE BOX OVERFILL 314.16 3. LABEL DISCONNECTS 4. IF SUPPORTED WHIPS & MC CABLE TO BE AS PER 300.11 5. VERIFY BOXES FOR BONDING PER 250.97 6. PLEASE PROVIDE INSTRUCTIONS FOR TRANSFORMERS MOUNTED ON BOXES 7. NOTE: BARRIERS WILL BE NEEDED IF MORE THAN 300V TO GROUND BETWEEN DEVICES. |
|
| 03/20/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |