Permit: T07CM00326

Parcel: 12701002C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00326

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/27/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
1. WAITING ON PAPERWORK FOR TRANSFORMERS
03/23/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/22/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6, 760.3 & 6
2. WE HAVE BOX OVERFILL 314.16
3. LABEL DISCONNECTS
4. IF SUPPORTED WHIPS & MC CABLE TO BE AS PER 300.11
5. VERIFY BOXES FOR BONDING PER 250.97
6. PLEASE PROVIDE INSTRUCTIONS FOR TRANSFORMERS MOUNTED ON BOXES
7. NOTE: BARRIERS WILL BE NEEDED IF MORE THAN 300V TO GROUND BETWEEN DEVICES.
03/20/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*