Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T07CM00324
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/08/2008 | FIRE - FINAL | Approved | ||
07/03/2008 | FIRE - FINAL | Approved | ||
12/24/2007 | FIRE - FINAL | Denied | ART ROOM EXIT DOOR #128 PASSAGE WAY DOOR TO REAR EXIT DOOR HAS A LOCKABLE DOOR KNOB, THIS IS NOT ALLOWED. THIS DOOR MUST REMAIN UNLOCKED AT ALL TIMES, REMOVED LOCKING DEVICE. RECEPITION OFFICE PASSAGE WAY DOOR TO REAR EXIT HAS A LOCKING TYPE DOOR KNOB THIS IS NOT ALLOWED, THIS DOOR MUST REMIAN UNLOCKED AT ALL TIMES. IFC 504.2 EXTERIOR DOORS CLOCKED SHALL BE LABEL WITH THE FOLLOWING ON THE OUTSIDE: "THIS DOOR BLOCKED" LETTERS HAVING A PRINCIPAL STORKE OF NOT LESS THAN 0.75 INCHES AND AT LEAST 6 INCHES HIGH ON A CONTRASTING BACKGROUND. NEED A UP TP DATE FIRE ALARM TEST, LAST ON FILE 2/2006 THIS IS TO BE DONE EVERY YEAR AND COPY SENT TO THE FIRE DEPARTMENT. |