Permit: T07CM00319

Parcel: 11308011A


Addresses:

3156 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00319

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SEE NOTE 12 ON CORRECTION SHEET
IN ADDITION TO PREVIOUS CORRECTIONS, WEATHERHEAD FOR SERVICE IS MISSING, STILL NEED TO MAKE ROOFTOP INSPECTION.
02/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL ADDRESS FOR SPACE (OUTSIDE DOORS)
2) GROUNDING ELECTRODE CONDUCTOR TO SERVICE HAS BEEN CUT/REMOVED
3) SEPERATE GROUNDS AND NEUTRALS IN SUB-PANELS AND PROVIDE ACCEPTABLE EQUIPMENT GROUND FOR SUB-PANELS
4) NEED GFI PROTECTION FOR BATH RECEPTACLES
5) USE ONLY SAME TYPE BREAKER IN PANEL (NOT SQUARED)
6) REPLACE/INSTALL ANY CRACKED OR MISSING DEVICES OR DEVICE COVERS
7) BACK RECEPTACLE SHOWS REVERSE POLARITY
8) PROPERLY IDENTIFY BOTH PANEL DIRECTORIES
9) HAVE OPEN WIRING IN J-BOXES ABOVE INTERIOR PANEL AND ABOVE FRONT DOOR ON EXTERIOR
10) REPLACE ALL RECEPTACLES THAT HAVE BEEN PAINTED
11) PROVIDE LADDER FOR ROOF TOP/CEILING INSPECTION
12) ALL WORK TO BE DONE BY A LICENSED ELECTRICAL CONTRACTOR ON SEPERATE PERMIT