Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00319
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE NOTE 12 ON CORRECTION SHEET IN ADDITION TO PREVIOUS CORRECTIONS, WEATHERHEAD FOR SERVICE IS MISSING, STILL NEED TO MAKE ROOFTOP INSPECTION. |
|
02/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ADDRESS FOR SPACE (OUTSIDE DOORS) 2) GROUNDING ELECTRODE CONDUCTOR TO SERVICE HAS BEEN CUT/REMOVED 3) SEPERATE GROUNDS AND NEUTRALS IN SUB-PANELS AND PROVIDE ACCEPTABLE EQUIPMENT GROUND FOR SUB-PANELS 4) NEED GFI PROTECTION FOR BATH RECEPTACLES 5) USE ONLY SAME TYPE BREAKER IN PANEL (NOT SQUARED) 6) REPLACE/INSTALL ANY CRACKED OR MISSING DEVICES OR DEVICE COVERS 7) BACK RECEPTACLE SHOWS REVERSE POLARITY 8) PROPERLY IDENTIFY BOTH PANEL DIRECTORIES 9) HAVE OPEN WIRING IN J-BOXES ABOVE INTERIOR PANEL AND ABOVE FRONT DOOR ON EXTERIOR 10) REPLACE ALL RECEPTACLES THAT HAVE BEEN PAINTED 11) PROVIDE LADDER FOR ROOF TOP/CEILING INSPECTION 12) ALL WORK TO BE DONE BY A LICENSED ELECTRICAL CONTRACTOR ON SEPERATE PERMIT |