Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00316
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO PROVIDE REVISED UPDATED SET OF DRAWINGS 2. NEED TO MEET WITH ELECTRICAL INSPECTOR ON SITE WHEN RECALL FOR INSPECTION. 3. TO AVOID REFEE PLEASE COMPLY WITH REQUESTS |
|
05/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : PROVIDE ACCURATE AS-BUILT DRAWING REFLECTING WHICH LIGHTS ON WHICH CIRCUITS AND LOADS. PLANS ON SITE DO NOT REFLECT ACTUAL ON SITE CONDITIONS. |
|
05/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
05/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE PRESENT TO ACCESS EQUIPMENT -- NEED REVISED AND STAMPED PLANS |
|
04/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN CALLS FOR FOUR NEW CIRCUITS TO BE ADDED TO PANEL B, NEITHER PANEL A OR B HAVE SPARE CIRCUITS. CONTRACTOR ADDED NEW LIGHTING TO EXISTING CIRCUITS, PLAN HAS TO BE REVISED TO SHOW THIS AND ALLOW ADDITION OF 11 PENDENT LIGHTS AND 14 NEW WALL WASHERS. PLANS WERE DRAWN WRONG COULD NOT INSTALL AS DRAWN |
|
03/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |