Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00314
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK REMAINDER PILLAR COVER |
|
04/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SCREWS NOT ALLOWED IN FRONT PORTION OF BOXES 314.23 2) TIGHTEN LOOSE FITTINGS |
|
03/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DISPLAY WINDOW WALLS |
|
03/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FILL UNUSED OPENING IN BOX 2) OK DEMISING WALL AND FAST COUNTER WALL 3) VDV CABELING TO BE PER 725.3 & 6, 760.3 & 6 AND 800.3 & 6 |