Permit: T07CM00311

Parcel: 11106055B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/19/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/15/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO COMPLETE ALL CORRECTIONS FROM PREVIOUS INSPECTION
2) IF ITEMS ARE NOT COMPLETE NEXT INSPECTION, A FEE MAY BE CHARGED
06/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED NAIL PLATE NEC 300.4
2) HAVE OVER FILLED BOXES NEC 314.16
3) USE PROPER CRIMP TOOL ON CRIMP SLEEVES NEC 110.3 (B)
4) SMOKE DETECTORS TO BE 36" AWAY MIN. FROM HVAC VENT NFPA 72
5) SCREWS NOT ALLOWED ON INSIDE OF BOXES NEC .23 B1
6) KITCHEN COUNTER CKTS AND DISPOSAL SHARED ? CHECK KITCHEN MAKE UP
7) GROUND ALL METAL BOXES NEC 250.148
8) CHECK RECEPTACLE SPACING NEC 210.52
9) CHECK SMOKE DETECTOR MOUNTING SHOULD BE WITHIN 12" OF CEILING NEC 110.3 B
10) HAVE ELECTRICIAN ON SITE FOR INSPECTION