Permit: T07CM00301

Parcel: 121092790

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM00301

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2007 FRAMING Approved IVRS - Inspection :*
09/18/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PORCH RAFTERS CANNOT BEAR ON SINGLE 2 X PLATE BY 4040 WINDOW
2) CONNECT ALL GROUND WIRES IN ELECTRIC BOXES AND SECURE WITH A MECHANICAL FASTNER. PROVIDE GROUND PIG TAILS FOR DEVICES
3) DRYER CIRCUIT MUST BE 3 WIRES PLUS GROUND AND USE A 4 PRONG PLUG
4) EXISTING ELECTRIC OUTLET CANNOT BE BURRIED IN WALL, INSTALL BOX EXTENSION
5) SMOKE DETECTOR REQUIRED IN HALL LEADING TO BEDROOM
6) GROUND ALL METAL ELECTRIC BOXES
09/17/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED STUD SHOE AT NOTCHED LAUNDRY STUD
2) GROUND ALL METAL BOXES
3) NAIL PROTECT ALL WIRING WITHIN 1 1/4" OF SURFACE
4) SHIM WHERE NEEDED
5) TAPE AND SECURE DRYER VENT