Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM00301
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PORCH RAFTERS CANNOT BEAR ON SINGLE 2 X PLATE BY 4040 WINDOW 2) CONNECT ALL GROUND WIRES IN ELECTRIC BOXES AND SECURE WITH A MECHANICAL FASTNER. PROVIDE GROUND PIG TAILS FOR DEVICES 3) DRYER CIRCUIT MUST BE 3 WIRES PLUS GROUND AND USE A 4 PRONG PLUG 4) EXISTING ELECTRIC OUTLET CANNOT BE BURRIED IN WALL, INSTALL BOX EXTENSION 5) SMOKE DETECTOR REQUIRED IN HALL LEADING TO BEDROOM 6) GROUND ALL METAL ELECTRIC BOXES |
|
| 09/17/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED STUD SHOE AT NOTCHED LAUNDRY STUD 2) GROUND ALL METAL BOXES 3) NAIL PROTECT ALL WIRING WITHIN 1 1/4" OF SURFACE 4) SHIM WHERE NEEDED 5) TAPE AND SECURE DRYER VENT |