Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK TO COVER ON MECHANICAL |
|
| 10/09/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* FLEX CONNECTIONS NOT PER DETAIL M5-1 NEED STRAPS ON FLEX FINISH INSULATING COND. PIPING ADD TURNING VANES TO ELBOWS DUCT NOT SEALED REATTACH STRAPS SEAL OSA AT ROOF PENETRATION SEAL OSA DUCT AT DANCE STUDIO INSTALL TURNING VANES PER DETAIL M5-3 INSTALL R/A GRILLS PER DETAIL PER M5.-2 OR PROVIDE LETTER OF APPROVAL FROM MECH. ENGINEER |
|
| 08/07/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |