Permit: T07CM00279

Parcel: 117031800


Addresses:

325 W 2ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/23/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK TO COVER ON MECHANICAL
10/09/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
FLEX CONNECTIONS NOT PER DETAIL M5-1
NEED STRAPS ON FLEX
FINISH INSULATING COND. PIPING
ADD TURNING VANES TO ELBOWS
DUCT NOT SEALED
REATTACH STRAPS
SEAL OSA AT ROOF PENETRATION
SEAL OSA DUCT AT DANCE STUDIO
INSTALL TURNING VANES PER DETAIL M5-3
INSTALL R/A GRILLS PER DETAIL PER M5.-2 OR PROVIDE
LETTER OF APPROVAL FROM MECH. ENGINEER
08/07/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*