Permit: T07CM00279

Parcel: 117031800


Addresses:

325 W 2ND ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/14/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
02/05/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) THERE MAYBE NO SYSTEM VENT BETWEEN FLOW CONTROL AND GREASE TRAP
2) OK TO COVER HAND SINK
3) FLOOR SINK REQUIRES CLEANOUT
01/30/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. DELTA SIX REVISION INDIRECTLY WASTES HAND SINK.
THIS IS NOT PER PLUMBING CODE. UPC REQUIRES HAND SINK TO BE DIRECTLY CONNECTED TO SS
2. FLOW CONTROL VENT MAY NOT TERMINATE INSIDE KITCHEN
3. 2 COMPARTMENTS OF 3-COMP SINK TO BE TRAPPED AND VENTED
4. VENT FITTINGS BELOW FLOOD RIM TO BE DRAINAGE TYPE
5. REQUIRE STRAINERS AT FLOOR SINKS
6. I.W PIPING TO HAVE MINIMUM 1" AIR GAP
01/17/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
OK TO COVER SHAMPOO BOWLS
01/11/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. AT SHAMPOO BOWL - EXCEPT IN THE CASE OF WYE BRANCH AND END OF THE LINE CLEANOUTS, CLEANOUTS SHALL BE INSTALLED ABOVE THE FLOW LINE OF THE PIPE

NOTE: A BLAKE TEE IS LISTED AS A VERTICAL SURFACE WALL CLEANOUT

2. ALL FIXTURES ARE TO BE DIRECTLY CONNECTED TO SANITARY SEWER. ONLY "SPECIAL" WASTE MAY BE INDIRECTLY WASTED I.E SANITIZING BOWL, FOOD PREP ETC.
3. GAS CARD CAN BE RELEASED AFTER BOND HAS BEEN POSTED
01/03/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. REMOVE COVER ON EWC
2. 2" CLEANOUTS REQUIRE 12" CLEARANCE IN FRONT
REMOVE 2" TEST PLUG AND INSTALL COUNTER SUNK
TAPPED PLUG W/MACHINE SCREW. REMOVE ALL CP CLEANOUT COVERS.
3. HAND SINK TO BE DIRECTLY CONNECTED TO SANITARY SEWER - DOES NOT MEET "SPECIAL WASTE" REQUIREMENT

CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
10/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEE TABLE 6-2 2003 UPC BACK SIPHONAGE/BACK PRESSURE LOW HAZARD EQUALS DOUBLE CHEEK VALVE BACKFLOW PREVENTOR
2. SHAMPOO BOWLS NOT COMPLETE
10/18/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*