Permit: T07CM00279

Parcel: 117031800


Addresses:

325 W 2ND ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/07/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
08/03/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
DOUBLE WYE MAY NOT BE INSTALLED IN THE HORIZONTAL POSITION
07/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- REDLINES ON SITE
- HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION
TO BE A SWEEP
- DOUBLE SANTEE REQUIRES BARREL OF FITTING TO BE TWO PIPE SIZES LARGER THAN LARGEST INLET
07/12/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
VERTICAL SUPPORT
HORIZONTAL SUPPORT
G.T FLOW CONTROL VENT
INSPECTION STOPPED
07/05/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NORMALLY YOU HAVE 03005 ROUGH/SOIL APPROVED
BEFORE INTERMEDIATE
2. GATE LOCKED NO ACCESS