Permit: T07CM00279

Parcel: 117031800


Addresses:

325 W 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/11/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CHECK EMERGENCY LIGHTING
2. PANEL 2C NOT PER PLAN
01/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. GO THROUGH AND AIM ALL EMERGENCY LIGHTS SO THEY WILL BE EFFECTIVE IF NEEDED
RECALL TO CONTINUE WITH FINAL INSPECTION
01/04/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP - KITCHEN AREA

1. IDENTIFY ALL EQUIPMENT
2. IDENTIFY DATA PLATES
3. SECURE WALK IN CONDENSOR TO ROOF
4. DISCONNECT "HP-2" TO HAVE PROPER FRONT WORKING CLEARANCE
5. PANEL DIRECTORIES TO BE CORRECT -
GO TO WHAT THEY SAY

INSPECTION FOR KITCHEN AREA -
1. PROVIDE DISCONNECTING MEANS FOR INSTA-HOT
2. DISHWASHER DISCONNECT TO HAVE PROPER FRONT CLEARANCE AND MOUNTED TO HIGH.
3. ABOVE WALK IN, SEAL INTERIOR OF RACEWAYS, STRAP FLEX, GROUND BOXES.