Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/21/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL WORK ABOVE CEILING BEFORE INSPECTION |
|
| 08/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FEEDER FROM PANEL DP TO PANEL 2A 2. OK FEEDER FROM PANEL DP TO PANEL A 3. OK FEEDER FROM PANEL A TO PANEL C 4. OK FEEDER FROM PANEL DP TO PANEL B 5. OK FEEDERFROM PANEL DP TO PANEL D 6. OK FEEDER FROM 1200 AMP SWITCH TO PANEL DP 7. PROVIDE APPROVED REVISION FOR CHANGES TO NEW SERVICE. 8. HAVE SERVICE UPGRADE ADDED TO ACTIVITY |
|
| 08/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER BOARDROOM WALL KITCHEN/WALK-IN AREA CEILINGS MISC. CEILING LIGHT AREAS - DANCE, BARBER |
|
| 07/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER PANEL A & B RACEWAYS OK KITCHEN IN WALLS OK MAIN CORRIDOR DRINKING FOUNTAIN & WEST WALLS OK BARBER SHOP WALLS (4 RECEPTACLES) OK RISER ROOM & FEEDER PULL BOX |
|
| 07/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER FEEDER RACEWAY ( 4 - 3" PVC) FROM SERVICE TO PANEL "DP" |
|
| 06/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EMT RUN IN RAFTER SECTION OF DINING ROOM 113 SO ROOF COULD BE INSTALLED. OPENED FROM ABOVE |