Permit: T07CM00279

Parcel: 117031800


Addresses:

325 W 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/29/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
COMPLETE ALL WORK ABOVE CEILING BEFORE INSPECTION
08/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK FEEDER FROM PANEL DP TO PANEL 2A
2. OK FEEDER FROM PANEL DP TO PANEL A
3. OK FEEDER FROM PANEL A TO PANEL C
4. OK FEEDER FROM PANEL DP TO PANEL B
5. OK FEEDERFROM PANEL DP TO PANEL D
6. OK FEEDER FROM 1200 AMP SWITCH TO PANEL DP
7. PROVIDE APPROVED REVISION FOR CHANGES TO NEW SERVICE.
8. HAVE SERVICE UPGRADE ADDED TO ACTIVITY
08/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER
BOARDROOM WALL
KITCHEN/WALK-IN AREA CEILINGS
MISC. CEILING LIGHT AREAS - DANCE, BARBER
07/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER PANEL A & B RACEWAYS
OK KITCHEN IN WALLS
OK MAIN CORRIDOR DRINKING FOUNTAIN & WEST WALLS
OK BARBER SHOP WALLS (4 RECEPTACLES)
OK RISER ROOM & FEEDER PULL BOX
07/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER FEEDER RACEWAY ( 4 - 3" PVC) FROM SERVICE TO PANEL "DP"
06/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK EMT RUN IN RAFTER SECTION OF DINING ROOM 113
SO ROOF COULD BE INSTALLED. OPENED FROM ABOVE