Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WEST SIDE STORAGE ROOM WALLS |
|
| 06/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO ENERGIZE PANEL A & B 2. NEED REVISION TO DRAWINGS SHOWING NEW POWER PLAN FOR SERVICE & FEEDERS. NEED TO SHOW LOAD CALCULATIONS, CONDUIT SIZE, FEEDER SIZE 3. O.R WIRING IN BEER CAVE. ENSURE RACEWAYS ARE SEALED PER NEC 300.7 4. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES ON TOP OF COOLERS PER NEC 110.12 |
|
| 06/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS & CEILING IN TWO RESTROOMS |
|
| 06/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH WALLS NEW OFFICE |